WXCTP-H CT PT Tester
Belongs to category: CT/PT Tester
Product Introduction
Transformer Tester is new product created after widely adopt customers’ advices and deep theoretical study. It is based on the automatic FA Series Transformer Tester General which is produced by our company that is widely acclaimed and applied. The adoption of high-performance DSP and ARM,advanced manufacturing technology ensure a stable and reliable product performance, full-featured, high degree of automation, high efficiency, in the domestic leading level, they are the professional testing equipments for transformer check in power industry.
Product names:CT parameter analyzer, CT analyzer, frequency CT analyzer, CTPT analyzer, transformer tester, frequency transformer characteristic tester, transformer transient characteristic analyzer, current transformer tester, CT characteristics analyzer, current transformer, current transformer parameters analyzer features analyzer, CT parameter tester, tester, current transformer, current transformer parameters characteristics tester, Comprehensive instrument for the transformer
Product Parameters
The main parameters
| Usage | Protection CT, protection PT |
| Output | 0~180Vrms,12Arms,18A(Peak) |
| Voltage measurement accuracy | ±0.2% |
| CT ratio measurement | Range:1~40000 |
| Accuracy: +0.2% ±0.05%(customizable) | |
| PT ratio measurement | Range:1~40000 |
| accuracy:±0.2% | |
| Phase measurement | The resolution of the: 0.5min |
| accuracy:±5min | |
| Secondary winding resistance measurement | Range:0~300Ω |
| accuracy:2%±2mΩ | |
| AC load measurement | Range:0~300VA |
| accuracy:2%±0.2VA | |
| power supply | AC220V±10%,50Hz |
| Working environment | emperature:-10c~50'c,humidity: ≤90% |
| Dimensions and weight | size: 340mmx220mmx330m, The weight of the: ≤9kg |
Product Characteristics
1、Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.
2、 Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.
3、Test meet IEC60044 GB1208 (-1) GB16847 (IEC60044-6) became etc all kinds of transformer standards, and in accordance with the transformer types and levels of automatic choose which standard test.
4、Based on the advanced low-frequency method to test principle of, it can deal with CT test with inflection point up to 30kV.
5、Interface friendly and beautiful, Chinese graphics interface.
6、The device can store 2000 sets of test data without loss when power is lost.After the test, use U disk to store it on the PC, analyze the data with the software, and generate WORD report.
7、The test is simple and convenient. The direct resistance, excitation, ratio change and polarity tests of CT are completed with one key. Besides the load test, all other tests of CT adopt the same wiring mode.
8、Easy to carry, device weight<9kg.
Keywords: WXCTP-H CT PT Tester
Previous: No more!
Next: WXFA-D CT PT Tester
Product Inquiry
Leave the information you want to consult, and we will contact you as soon as possible