WXRS AC Resonant Test System For Substation
Belongs to category: Series Resonant Voltage Withstand Device
Product Introduction
Transformer, GIS, SF6 switch, CT/PT, insulator, bus bar, cable, bushing, and others capacitive devices are the common primary electric equipment. Composed by power control cabinet, excitation transformer, reactor, voltage divider, connects silicon rectifier stack and micro ammeter with the voltage divider, then can finish the DC voltage withstand test.
Product Characteristics
◆It with smaller volume, lighter weight compared with others reactors which in same voltage class and capacity. With small temperature rise under rated load; strong mechanical strength, good insulation performance, reliable.
◆The capacity of the power control cabinet is high; strong protection function; good output waveform; good stability; multi-function, easy to operate; single phase 220V or three phase 380V are available.
◆Can match different kinds reactors, multifunctional, highly cost effective.
Product Parameters
| Rated output voltage | 0~1000kV |
| Output frequency | 30~300Hz |
| Voltage waveform | Sine wave,distoration≤1.0% |
| Working form | Full power continuous working time 60min |
| Quality factor | 30~90 |
| Frequency adjustment sensitivity | 0.1Hz |
| Instability | <0.05% |
| Power supply | Single phase 220V or three phase380V±10% |
| Frequency: 50Hz±5% |
Serial product and application:
| Model | Application(10kV~500kV transformer substation AC voltage withstand equipment, frequency: 30~300Hz ) | ||||
| Frequency power source | Resonant reactor | Excitation transformer | Divider | Application | |
| WXTF-50/50/25 | 3kW | 25kV/1A:2 sets( dry type ) | 3kVA( dry type ) | 50kV | 10kV transformer ≤1000kVA 10kVswitch, bus bar, PT,CT, etc. 10kV(300mm2)cable≤1.0km |
| WXTF-108/108/27 | 5kW | 27kV/1A:4 sets( dry type ) | 5kVA( dry type ) | 110kV |
35kV transformer ≤31500kVA 35kV switch, bus bar, PT,CT, etc. |
| WXTF-200/200/50 | 10kW | 50kV/1A:4 sets( dry type ) | 10kVA( dry type ) | 200kV | 110kVtransformer≤ 50000kVA 110kVGIS,PT,CT, etc.(preventive trial) 35kV(300mm2)cable≤1.0km 10kV (300mm2)cable≤2.0km |
| WXTF-270/270/45 | 15kW | 45kV/1A:6 sets( dry type ) | 15kVA( dry type ) | 300kV | 110kVtransformer≤ 50000kVA 110kVGIS,PT,CT, etc. 35kV(300mm2)cable≤1.2km 10kV (300mm2)cable≤3.0km |
| WXTF-800/400/50 | 30kW |
50kV/2A:8 sets ( dry type ) (oil immersed) |
30kVA( dry type ) |
400kV |
220kV transformer ≤80000kVA 110kVtransformer≤ 50000kVA |
| WXTF-1600/800/200 | 60kW |
200kV/2A:4 sets (oil immersed) |
60kVA( dry type ) | 800kV |
220kV transformer ≤80000kVA 110kVtransformer≤ 50000kVA |
Note: can make the solution according the parameters of the measured equipment