WXJF-S Partial Discharge Analysis Testing Equipment
Belongs to category: Partial Discharge Test System
Product Introduction
WXJF-S is widely used in the partial discharge detection of power systems. Including high voltage switchgear, ring mains, voltage/current transformer, transformer (include dry type transformer), GIS, overhead lines, cables, and other equipment insulation state detection.
The following indicators are used to measure the degree of discharge of electrical equipment:
Partial discharge intensity detection: By measuring the discharge signal in a power frequency cycle, the intensity of the partial discharge is characterized according to the maximum value (dB) in the discharge pulse sequence.
Partial discharge frequency detection: The device measures the discharge signal within a power frequency cycle, extracts the discharge pulses and characterizes the frequency of partial discharges according to the number of discharge pulses.
Product Characteristics
● With different sensors to achieve partial discharge detection of almost all electrical equipment.
● Provide multiple discharge patterns such as time-domain waveform, PRPD, PRPS, etc., to realize the analysis of different discharge types.
● User-friendly man-machine interface facilitates the data management of different devices, including the traceability of historical data change trends, horizontal and vertical data analysis, and realizes a 360° comprehensive diagnosis of the tested device.
● Built-in ultrasonic sensor and transient earth voltage (hereinafter referred to as TEV) sensor, also can be connected to external special sensors for transformers, GIS, overhead lines, and cables.
● It adopts non-intrusive detection method, no need to power off during the test process, no need to configure additional high voltage source, it is more convenient to use than traditional pulsed partial discharge detector.
● The test bandwidth range is 30kHz ~ 2.0GHz, suitable for detection principles of various frequency bands.
Product Parameters
| TEV Measurement | UHF Measurement | ||
| Measurement range | 0-60dBmV | Detection frequency band | 300~1500MHz |
| 300~1500MHz | 1dB | Measurement range | -75-0dBmV |
| Accuracy | ±1dB | Accuracy | <1dBmV |
| Max. pulse per cycle | 1400 | Sensor frequency band | 300-2000MHz |
| Measurement frequency band | 1~100MHz | ||
| AA measurement | AE measurement | ||
| Measurement range | -6dBμV~68dBμV | Measurement range | -6dBμV~68dBμV |
| Resolution | 1dB | Resolution | 1dB |
| Accuracy | ±1dB | Accuracy | ±1dB |
| Sensor center frequency | 40kHz | Frequency range | 40-200kHz |
| HFCT measurement | |||
| Sensor transmission impedance | 5mV/mA | ||
| Detection frequency | 1~30MHz | ||
| Sensitivity | ≤50pC | ||
| Hardware | |||
| Shell | ABS | ||
| Display | 4.0inch RGB LCD screen | ||
| Controller | ARM | ||
| Connector | USB interface (charger port), Wireless WIFI 3.5mm stereo headphone jack, Wireless synchronization benchmark External ultrasonic sensor input | ||
| Headphone | 8ohm minimum | ||
| SD card | Standard 16G | ||
| Built-in battery | 3.7V/1Ah lithium battery | ||
| Working time | About 8 hours | ||
| Charger | AC 90-264V or DC 5V | ||
| Working temperatures | -20~+50℃ | ||
| Humidity | 20~85% relative humidity | ||
| Dimension, weight | 210*100*35(mm), 0.4kg (main unit) | ||
Packing List
| Main unit | Standard |
| External Contact ultrasonic sensor | For option, used for transformers, GIS, motors |
| UHF sensor | For option, used for GIS |
| HFCT | For option, used for power cable |
| Test cable | Standard |
| Charger | Standard |
| USB cable | For charging and PC communication |
| User’s guide | |
| Factory test report |
FAQ
1.When can I get the price?
We usually quote within 6 hours after we get your inquiry.
If you are very urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.
2. What about the leading time for production?
Honestly, it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.
3. What is your payment terms?
We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.
4. How much will be the Shipping cost and time?
This will depend on the size of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.
5. Could you please tell me the Warranty Period of your product?
Our warranty period is one year free and lifelong maintenance. If the product is damaged (if not man-made damage), in the first year,we will send free parts for replacement. Over warranty, maintenance is paid service.
6. What kind of Certificate can you provide?
We can provide the CE mark, ISO 9001 quality certificate, third party calibration certificate(CNAS) and factory test report.
7. Do you have Technical Backup to all customers from different countries?
To be sure,our technical support is always available and quick response.
We are manufacturer with much on-site testing experience, thus we know how to deal with your problems. Moreover, our engineers can go to your country to support if need.
Keywords: WXJF-S Partial Discharge Analysis Testing Equipment
Next: No more!
Product Inquiry
Leave the information you want to consult, and we will contact you as soon as possible