WXMG3000B Three-Phase Intelligent Phase and Volt-Ammeter
Belongs to category: Intelligent Phase and Volt-Ammeter
Introduction
The WXMG3000B Three-Phase Intelligent Phase and Volt-Ammeter is a versatile smart meter specifically designed for on-site testing. It consists of a main unit, current clamps (3), test leads (4), and other components. The main unit features a 3.5-inch true-color LCD screen with a graphical menu interface and phasor diagram display, making readings clear and intuitive. The current clamps are designed with compact, narrow jaws for easy operation, making them highly suitable for use in areas with densely arranged wires.
The WXMG3000B allows for simultaneous measurement of various three-phase AC parameters without breaking the circuit under test. Its capabilities include measuring voltage, current, phase angles between voltages, between currents, and between voltage and current, frequency, phase sequence, active power, reactive power, apparent power, power factor, and current vector sum. It can be used to identify transformer connection groups, determine if a circuit is inductive or capacitive, test secondary circuits and busbar differential protection systems, read the phase relationships between CTs in differential protection groups, check the correctness of watt-hour meter wiring, and troubleshoot line equipment. It provides a safe, accurate, and convenient intelligent instrument for electricity inspection personnel. It is suitable for applications in electric power, petrochemicals, metallurgy, railways, meteorology, industrial and mining enterprises, research institutes, universities, and metrology departments. It is particularly well-suited for use in electricity billing systems and relay protection systems.
Technical Specifications
1、Reference Conditions and Operating Conditions
| Influence Quantity |
Reference Condition |
Operating Condition |
Remarks |
| Ambient Temperature |
23℃ ± 1℃ |
-10℃ ~ 40℃ |
/ |
| Ambient Humidity |
40% ~ 60% |
< 80% |
/ |
| Signal Waveform |
Sine wave |
Sine wave |
β = 0.01 |
| Signal Frequency |
50 Hz ± 1 Hz |
45 Hz ~ 65 Hz |
/ |
| Meter Operating Voltage |
7.4V ± 0.5V |
7.4V ± 1V |
/ |
| Current Amplitude (for measuring Phase, Frequency, Phase Sequence) |
1A ± 0.1A |
1mA ~ 30A |
Refer to General Specifications |
| Voltage Amplitude (for measuring Phase, Frequency, Phase Sequence) |
100V ± 10V |
1V ~ 600V |
/ |
| Current Amplitude (for measuring Power, Power Factor) |
1A ± 0.1A |
10mA ~ 30A |
/ |
| Voltage Amplitude (for measuring Power, Power Factor) |
100V ± 10V |
10V ~ 600V |
/ |
| External Electric/Magnetic Fields |
Should be avoided |
||
| Position of Conductor under Test |
Conductor should be positioned near the geometric center of the clamp jaws |
||
2、General Specifications
| Function | Simultaneously measures current, voltage, phase, frequency, phase sequence, active power, reactive power, apparent power, power factor, and current vector sum in three-phase 380V/220V power systems; identifies transformer connection groups, inductive/capacitive circuits; tests secondary circuits and bus differential protection systems; reads phase relationships between CTs in differential protection groups; checks correctness of watt-hour meter wiring; troubleshoots line equipment, etc. |
| Power Supply | DC 7.4V large-capacity rechargeable lithium battery, USB charging port, provides approximately 10 hours of continuous operation on a full charge. |
| Rated Current | Approx. 180mA Max |
| Display Mode | 3.5-inch true-color LCD display |
| Unit Dimensions (L×W×H) | 196mm × 92mm × 54mm |
| Clamp Jaw Size | φ7.5mm × 13mm |
| Sampling Rate | Approx. 3 times/second |
| Measurement Range | AC Voltage: 0.00V ~ 600V |
| AC Current: 0.0mA ~ 30A | |
| Phase: 0.0° ~ 360.0° | |
| Frequency: 45.00Hz ~ 65.00Hz | |
| Active Power: 0.0W ~ 12kW | |
| Reactive Power: 0.0VAR ~ 12kVAR | |
| Apparent Power: 0.0VA ~ 12kVA | |
| Power Factor: -1 ~ +1 | |
| Current Vector Sum: 0mA ~ 60A | |
| Resolution | Voltage: AC 0.01V |
| Current: AC 0.1mA | |
| Phase: 0.1° | |
| Frequency: 0.01Hz | |
| Active Power: 0.1W | |
| Reactive Power: 0.1VAR | |
| Apparent Power: 0.1VA | |
| Power Factor: 0.001 | |
| Current Vector Sum: 1mA | |
| Accuracy (Under Reference Conditions) | Voltage: ±(0.5% of reading) |
| Current: ±(0.5% of reading) | |
| Phase: ±1° (Phase error under operating conditions: ±3° for 10mA~30A; ±5° for <10mA. For accurate current-phase measurement with currents below 5mA, voltage measurement is not recommended. For voltage-current phase tests, ensure voltage ≥5V and current ≥5mA for reliable results.) | |
| Active Power: ±(1.0% of reading) | |
| Reactive Power: ±(1.0% of reading) | |
| Apparent Power: ±(1.0% of reading) | |
| Frequency: ±(1.0% of reading) | |
| Power Factor: ±0.03 | |
| Phase Sequence Indication | Positive Sequence: U1, U2, U3 or I1, I2, I3 cursors blink sequentially left to right. |
| Reverse Sequence: U1, U2, U3 or I1, I2, I3 cursors blink sequentially right to left. | |
| Detection Speed | Approx. 2 seconds/measurement |
| Data Hold | Press HOLD key to hold data during measurement; "HD" icon displayed. |
| Data Storage | 99 groups |
| Charging Port | USB charging port |
| Auto Power Off | Powers off automatically after approx. 15 minutes of inactivity to conserve battery. |
| Backlight | Yes, adjustable brightness |
| Voltage Detection | Low battery symbol displayed when voltage falls below 6.5V, prompting recharge. Auto power-off within 10 seconds. |
| Weight | Main Unit: 350g (including battery) |
| Current Clamps: 170g × 3 | |
| Total Weight: Approx. 1.35kg | |
| Test Lead Length | 1.5m |
| Current Clamp Cable Length | 2m |
| Operating Temp. & Humidity | -10℃ ~ 40℃; Below 80% RH |
| Storage Temp. & Humidity | -10℃ ~ 60℃; Below 70% RH |
| Input Impedance | Voltage input impedance: 1MΩ |
| Withstand Voltage | 1000V/50Hz AC sine wave for 1 minute between terminals and enclosure. |
| Insulation Resistance | ≥100MΩ between terminals and protective enclosure. |
| Compliance/Safety Standards | IEC61010-1 CAT III 600V, IEC61010-031, IEC61326, Pollution Degree 2 |
FAQ
1.When can I get the price?
We usually quote within 6 hours after we get your inquiry.
If you are very urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.
2. What about the leading time for production?
Honestly, it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.
3. What is your payment terms?
We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.
4. How much will be the Shipping cost and time?
This will depend on the size of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.
5. Could you please tell me the Warranty Period of your product?
Our warranty period is one year free and lifelong maintenance. If the product is damaged (if not man-made damage), in the first year,we will send free parts for replacement. Over warranty, maintenance is paid service.
6. What kind of Certificate can you provide?
We can provide the CE mark, ISO 9001 quality certificate, third party calibration certificate(CNAS) and factory test report.
7. Do you have Technical Backup to all customers from different countries?