WXDJ-DGA Transformer Oil Chromatographic Online Monitoring System
Belongs to category: Transformer Oil Chromatographic Analysis Equipment
System Overview
The WXDJ-DGA Transformer Oil Chromatographic Online Monitoring System is a cost-effective online oil-gas monitoring system that requires no carrier gas. It utilizes an advanced ceramic membrane degassing module (patented), featuring a compact design and short oil-gas equilibrium time. The system employs an array-type gas sensor capable of detecting characteristic gases dissolved in oil, such as H₂, CO, C₂H₂, and C₂H₄. The combination of innovative sensors and advanced algorithms ensures that the system's accuracy and stability meet internationally leading standards. Additionally, it can be extended to monitor trace moisture in oil and transformer core leakage current, with on-site LCD display functionality. It is characterized by accurate measurement, rapid analysis, and real-time monitoring.
The system is primarily used to measure and analyze trace fault gases dissolved in the insulating oil of oil-immersed power equipment. It can capture potential fault information in transformer equipment in real time, ensuring reliable operation.
Instrument Functions and Technical Features
Easy Installation, No Power Outage Required: The device is compact and lightweight, allowing direct installation on the transformer's DN50 or DN80 flange. Oil sampling and return are integrated via a gear pump for circulation and agitation, enabling the online monitor to promptly reflect internal transformer faults.
Short Monitoring Cycle, Reflecting True Transformer Condition:It features the innovative application of a ceramic membrane component, resulting in a short equilibrium time. The oil pump circulation method is employed, ensuring that the extracted gases accurately represent the actual condition of the transformer.
Integrated Device Design Philosophy: The device can operate independently without a background computer. It features a high level of integration, automatic analysis functions, and includes communication and alarm interfaces for direct connection to a background system or DCS.
Automatic Sensor Zero-Drift Calibration: Gas sensors can drift over time, leading to measurement errors. Compared to current transformer online monitoring products on the domestic and international markets, this product's major technological innovation is its ability to automatically calibrate sensor zero-drift before each measurement.
Novel Field Device Structural Design: The sampling port is located externally for convenient oil sampling. The device offers protection against lightning, rain, humidity, high temperatures, and other environmental factors.
LCD Display: Features scrolling LCD display functionality.
Flexible Communication Methods, Clearly Displaying Key Parameters and Status: Supports both wired and wireless communication, enabling networked online monitoring of multiple transformers. Optional 4G SMS function allows users to receive field detection data on their mobile phones in real time, achieving true unattended operation.
Strong Anti-Interference, Stable Performance: The device meets the requirements for operation in various harsh outdoor environments while resisting electromagnetic fields and radio wave interference in substations. It has passed electromagnetic compatibility (EMC) tests at national quality inspection centers.
Convenient Maintenance: Compared to online chromatographic instruments, it requires no regular replacement of consumables like carrier gas and no periodic instrument calibration.
Technical Parameters and Specifications
(Note: Oil Temperature, Trace Moisture, and Core Leakage Current are optional parameters.
| Technical Parameter | Specification |
|---|---|
| Measured Components | H₂, CO, C₂H₄, C₂H₂, Oil Temp., Trace Moisture, Core Current* (*Optional) |
| Degassing Method | Advanced ceramic membrane degassing; 2-hour oil-gas equilibrium; service life >5 years |
| Pressure Rating | 0 ~ 0.3 MPa |
| Power Supply | 220 V / 50 Hz AC (≥2 A) |
| Alarm Output | Audio/visual alarm on background PC; device provides dry contact alarm output |
| Data Communication | RS-485 (MODBUS) / IEC 61850 (Optional) |
| Communication Distance | RS-485: 1000 m |
| Transformer Oil Temp. Range | 15°C ~ 85°C |
| Operating Ambient Temp. | -40°C ~ +70°C |
| Operating Relative Humidity | 5% ~ 95%, non-condensing |
| Storage Temperature | -30°C ~ +75°C |
| Device Dimensions (L×W×H) | 260 mm × 340 mm × 170 mm |
| Device Weight | 10 kg |
Technical Specifications
| Parameter | Measurement Range(μL/L) | Measurement Error Limit |
| Hydrogen (H₂) | 2-1000 | ±2 μL/L or ±30% |
| Carbon Monoxide (CO) | 5-2000 | ±25 μL/L or ±30% |
| Acetylene (C₂H₂) | 0.5-20 | ±0.5 μL/L or ±30% |
| Ethylene (C₂H₄) | 0.5-200 | ±0.5 μL/L or ±30% |
| Oil Temperature | -190 | ±0.2 or 1% |
| Trace Moisture | 0-100 | ±0.5 or ±1% |
| Core Leakage Current | 0-1000 | +0.05 or 0.5% |
FAQ
1.When can I get the price?
We usually quote within 6 hours after we get your inquiry.
If you are very urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.
2. What about the leading time for production?
Honestly, it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.
3. What is your payment terms?
We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.
4. How much will be the Shipping cost and time?
This will depend on the size of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.
5. Could you please tell me the Warranty Period of your product?
Our warranty period is one year free and lifelong maintenance. If the product is damaged (if not man-made damage), in the first year,we will send free parts for replacement. Over warranty, maintenance is paid service.
6. What kind of Certificate can you provide?
We can provide the CE mark, ISO 9001 quality certificate, third party calibration certificate(CNAS) and factory test report.
7. Do you have Technical Backup to all customers from different countries?
To be sure,our technical support is always available and quick response.
We are manufacturer with much on-site testing experience, thus we know how to deal with your problems. Moreover, our engineers can go to your country to support if need
Keywords: WXDJ-DGA Transformer Oil Chromatographic Online Monitoring System
Previous: No more!
Product Inquiry
Leave the information you want to consult, and we will contact you as soon as possible