Get in touch

Are you interested in our products or services? Contact us immediately, our experts will provide you with professional services!

*Please leave your specific personal information, and we will have a product consultant contact you later

Submit
%{tishi_zhanwei}%
WXDJ‑DGA Online Oil Chromatographic Analysis System
+
  • WXDJ‑DGA Online Oil Chromatographic Analysis System

WXDJ‑DGA Online Oil Chromatographic Analysis System


Display Content H₂, CO, CH₄, C₂H₆, C₂H₂, C₂H₄, CO₂ (optional), moisture (optional) Analysis Cycle System default: 12 hours per cycle; user‑adjustable Data Storage Depends on hard disk capacity Temperature Control Accuracy ±0.2 °C Ambient Temperature ‑40 °C ~ +80 °C Relative Humidity 5 % – 95 %, non‑condensing

Belongs to category: Transformer Oil Chromatographic Analysis Equipment

Product Introduction

The transformer oil online monitoring system is primarily designed to detect and measure trace fault gases in the oil of oil-immersed electrical equipment, enabling early warning of potential equipment defects, preventing sudden failures, and enhancing the safety and reliability of power system operation.

The WXDJ‑DGA Online Oil Chromatographic Analysis System can simultaneously detect seven characteristic fault gases in transformer oil: hydrogen (H₂), carbon monoxide (CO), methane (CH₄), carbon dioxide (CO₂), ethylene (C₂H₄), ethane (C₂H₆), and acetylene (C₂H₂). In addition, it can be optionally equipped to measure moisture content in oil upon user request.

This Online Oil Chromatographic Analysis System consists of three modules: a power supply module, a degassing module, and an analysis and detection module. The degassing module is directly connected to the transformer tank or the oil return pipeline via an oil pump, drawing transformer oil into the module. The degassing module separates the gases from the oil and then delivers the extracted gas to the chromatographic column, which separates the various characteristic gases for detection. The power supply module supplies electrical power to the entire system. The data collected by the online monitoring system are transmitted via an RS‑485 bus or TCP/IP to the system analysis and management software for further processing.

The recommended default sampling cycle for the online oil chromatography analyzer is once every 12 hours. Users can reset the sampling cycle through the host computer based on the actual operating conditions of the transformer.

The diagnostic analysis software is a 64‑bit Windows application, compatible with Windows 7 and later. It does not require routine manual intervention on the host computer or the instrument by management personnel; instead, it automatically performs data acquisition, trend analysis and rate‑of‑change analysis of the fault gas data, and automatically generates daily reports, historical data reports, as well as data trend curves.

Product Parameters

ItemSpecification
Detection PrincipleBroad‑spectrum gas chromatography, simultaneously detecting H₂, CO, CH₄, C₂H₂, C₂H₆, C₂H₄, total hydrocarbons, carbon dioxide (optional), and moisture (optional)
Detection ItemsTotal hydrocarbons, carbon dioxide (optional), moisture (optional)
Temperature ControlConstant temperature control
Field CommunicationRS‑485 bus, Industrial Ethernet, optical fibre
Network ProtocolSupports TCP/IP protocol; supports remote monitoring and remote maintenance
Display ContentH₂, CO, CH₄, C₂H₆, C₂H₂, C₂H₄, CO₂ (optional), moisture (optional)
Analysis CycleSystem default: 12 hours per cycle; user‑adjustable
Data StorageDepends on hard disk capacity
Temperature Control Accuracy±0.2 °C
Ambient Temperature‑40 °C ~ +80 °C
Relative Humidity5 % – 95 %, non‑condensing
Solar Radiation Intensity1 kW/m² (at wind speed 0.5 m/s)
Altitude< 3000 m
Ice Coating Thickness20 mm (when wind speed ≤ 15 m/s)
Power SupplyAC 220 V ± 10 %, 50 Hz, ≤ 900 W
Carrier GasHigh‑purity air
Dimensions1200 (H) × 800 (W) × 600 (D) mm
Vibration Resistance5–17 Hz: 0.1″ double‑amplitude displacement; 17–640 Hz: 1.5 G peak‑to‑peak acceleration
Shock ResistanceAcceleration: 10 G peak‑to‑peak

Measurement Range of Online Oil Chromatographic Analysis System

ParameterDetection Range (μL/L)ResolutionAccuracy
Hydrogen (H₂)2 – 20001 μL/L≤ ±30 %
Acetylene (C₂H₂)0.5 – 10000.1 μL/L≤ ±30 %
Methane (CH₄), Ethylene (C₂H₄), Ethane (C₂H₆)0.5 – 10000.1 μL/L≤ ±30 %
Carbon Monoxide (CO)25 – 50001 μL/L≤ ±30 %
Carbon Dioxide (CO₂)25 – 150001 μL/L≤ ±30 %
Total Hydrocarbons (C₁+C₂)2 – 40001 μL/L≤ ±30 %
Moisture (optional)1 – 1001 μL/L≤ ±30 %
Monitoring Cycle12 hours/cycle, 2 hours per analysis
Sampling MethodQuantitative sampling
Degassing MethodVacuum degassing
Impurity RemovalRefrigeration
Injection MethodAutomatic injection
Separation MethodGas chromatography
Detection MethodGas chromatography
Display MethodComputer
Analysis & DiagnosisComputer
Alarm MethodComputer
Communication ModeRS‑485 bus / Industrial Ethernet / Optical fibre
Communication ProtocolSupports TCP/IP, remote monitoring and remote maintenance
Standard Carrier GasHigh‑purity air
Power SupplyAC 220 V ± 10 %, 50 Hz, ≤ 900 W

FAQ

1.When can I get the price?

We usually quote within 6 hours after we get your inquiry.

If you are very urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.

2. What about the leading time for production?

Honestly, it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.

3. What is your payment terms?

We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.

4. How much will be the Shipping cost and time?

This will depend on the size of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.

5. Could you please tell me the Warranty Period of your product?

Our warranty period is one year free and lifelong maintenance. If the product is damaged (if not man-made damage), in the first year,we will send free parts for replacement. Over  warranty, maintenance is paid service.

6. What kind of Certificate can you provide?

We can provide the CE mark, ISO 9001 quality certificate, third party calibration certificate(CNAS) and factory test report.

7. Do you have Technical Backup to all customers from different countries?

To be sure,our technical support is always available and quick response.
We are manufacturer with much on-site testing experience, thus we know how to deal with your problems. Moreover, our engineers can go to your country to support if need.

 

 

Keywords: WXDJ‑DGA Online Oil Chromatographic Analysis System

Product Inquiry

Leave the information you want to consult, and we will contact you as soon as possible

Inquiry